SYSTEM MODEL NO.
UNITS
S24CC
PERFORMANCE RATINGS
Capacity
BTU/h
22600/22000
SEER
-
10.20
Moisture Removal
Pts/h
6.6
Air Flow (High)/Throw (*)
CFM
510/30
Sensible Heat Ratio (SHR)
-
0.69
Sound Rating Outdoors
Bels
7.6
ELECTRICAL DATA
Power Source
-
230/208-60-1
Minimum Ampacity
A
16
Total Input
W
2460/2415
Maximum TD Fuse/HACR Breaker
A
25
REFRIGERATION LINES
Connections
-
FLARE
Liquid O.D.
in
1/4
Suction O.D.
in
5/8 (See note below)
Factory Pre-charge
ft
25
Maximum Length (**)
ft
50
Maximum Height Difference
ft
33
DIMESIONS & WEIGHT
Indoor Unit
Model #
MS24C3
Width
in
46 1/16
Height
in
7 11/16
Depth
in
25 9/16
Net Weight
lbs
68
Shipping Weight
lbs
79
OutDoor Unit
Model #
MR24C3C
Width
in
33
Height
in
25 11/16
Depth
in
13 1/4
Net Weight
lbs
135
Shipping Weight
lbs
145

(*) Air throw data is representative of the maximum coverage. Location of unit, size of room, etc. will affect coverage

(**) Maximum line lengths may be extended up to 80 feet with field-installed accumulators. Contact Friedrich for specifications.

Back to top

NOTE:
Indoor section has 1/2" O.D. connection. 5/8" to 1/2" reducer required

Standard Rating Conditions
Outside Temperature 95°F dry bulb
Inside Temperature 80°F dry bulb
67°F wet bulb


|Wallmount (Single Zone) | Wallmount (Dual Zone) | Wallmount (Dual-Zone Cooling) | 2' x 4' T-Bar Ceiling |

| Home Page | E-Mail Form |


Due to continuing research in new energy-saving technology, specifications are subject to change without notice.